Thông số kỹ thuật ABB RVC-8

RVC
 Measuring system  Micro-processor system for balanced three-phase networks or single-phase networks
Operating voltage 100V to 440V
Frequency range 50 or 60 Hz
Current input 1A or 5A (RMS)
Current input impedance <0.1 Ohm (recommended CT class 1.0, 10 VA min)
Consumption 8 VA max
Output contact rating Max. continuous current: 1.5A
Max. peak current: 5A
Max. voltage: 440 Vac
Terminal A is rated for a continuous current of 16A
 Alarm contact Normally open contact
Max. continuous current: 5A
Rated/max. breaking voltage: 250Vac/440Vac
Starting current setting (C/k) 0.01 to 3A
Automatic measurement of C/k
Number of outputs From 3 to 12 outputs
Power Factor setting From 0.7 inductive to 0.7 capacitive
Switching sequences User defined
Power outage release Quick automatic disconnection in less than 20ms (50Hz) in case of power outage or voltage drop
Power outage reset delay time 40s
Operating temperature -10°C to 60°C
Storage temperature -30°C to 85°C
Dimensions (HxWxD) and weight 144x144x43 – 0.4 kg (unpacked)
Front plate protection IP43