Mô đun Abb AI880A
Thông số kỹ thuật module đầu vào Abb AI880A
đại lý AI880A | nhà phân phối AI880A
Thông số kỹ thuật chung module truyền thông Abb
| Mã đặt hàng | 3BSE039293R1 |
| Type | Analog Input |
| Signal specification | 0..20 mA, 4..20 mA |
| Số kênh | 8 |
| Signal type | Unipolar single ended |
| HART | Yes |
| SOE | No |
| Redundancy | Yes |
| High integrity | Yes |
| Intrinsic safety | No |
| Mechanics | S800 |
đại lý abb | đại lý 3BSE039293R1
nhà phân phối abb | nhà phân phối 3BSE039293R1
Dữ liệu chi tiết
| Resolution | 12 bit |
| Input impedance | 250 Ω with shunt stick TY801 (at current input) |
| Isolation | Groupwise isolated from ground |
| Under/over range | Over range: +12% (0..20 mA), +15% (4..20 mA) |
| Error | Max. 0.1% |
| Temperature drift | Max. 50 ppm/°C |
| Input filter (rise time 0-90%) | 190 ms (HW filter) |
| Update cycle time | 10 ms |
| Current limiting | Built in current limited transmitter power |
| Maximum field cable length | 600 meters (656 yards) |
| Max input voltage (non destructive) | 11 V d.c. |
| NMRR, 50Hz, 60Hz | > 40 dB |
| Rated insulation voltage | 50 V |
| Dielectric test voltage | 500 V a.c. |
| Sự thât thoát năng lượng | 2.4 W |
| Current consumption +5 V Modulebus | 45 mA |
| Current consumption +24 V Modulebus | max 50 mA |
| Current consumption +24 V external | 4 + transmitter current mA, max 260 mA |
Environment and certification
| CE mark | Yes |
| Electrical safety | IEC 61131-2, UL 61010-1, UL 61010-2-201 |
| Hazardous Location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
| Marine certification | ABS,BV,DNV-GL,LR |
| Protection rating | IP20 according to IEC 60529 |
| Corrosive atmosphere ISA-S71.04 | G3 |
| Climatic operating conditions | 0 to +55 °C (Storage -40 to +70 °C), RH=5 to 95 % no condensation, IEC/EN 61131-2 |
| Pollution degree | Degree 2, IEC 60664-1 |
| Mechanical operating conditions | IEC/EN 61131-2 |
| EMC | EN 61000-6-4 and EN 61000-6-2 |
| Overvoltage categories | IEC/EN 60664-1, EN 50178 |
| Equipment class | Class I according to IEC 61140; (earth protected) |
| Max ambient temperature | 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) |
| RoHS compliance | DIRECTIVE/2011/65/EU (EN 50581:2012) |
| WEEE compliance | DIRECTIVE/2012/19/EU |