Mô đun Abb AO801
Thông số kỹ thuật module đầu ra tương tự Abb AO801
đại lý AO801 | nhà phân phối AO801
Thông số kỹ thuật chung module truyền thông Abb
| Mã đặt hàng | 3BSE020514R1 |
| Type | Analog Output |
| Signal specification | 0… 20 mA, 4…20 mA |
| Số kênh | 8 |
| Signal type | Unipolar single ended |
| HART | No |
| SOE | No |
| Redundancy | No |
| High integrity | No |
| Intrinsic safety | No |
| Mechanics | S800L |
đại lý abb | đại lý 3BSE020514R1
nhà phân phối abb | nhà phân phối 3BSE020514R1
Dữ liệu chi tiết
| Resolution | 12 bit |
| Isolation | Groupwise isolated from ground |
| Under/over range | – / +15% |
| Output load | Max 850 Ω |
| Error | 0,1 % |
| Temperature drift | Typ 30 ppm/°C, Max 50 ppm/°C |
| Rise Time | 10 µs |
| Update cycle time | 1 ms |
| Current limiting | Short circuit proof current limited output |
| Maximum field cable length | 600 meters (656 yards) |
| Rated insulation voltage | 50 V |
| Dielectric test voltage | 500 V a.c. |
| Sự thât thoát năng lượng | 3.8 W |
| Current consumption +5 V Modulebus | 70 mA |
| Current consumption +24 V Modulebus | – |
| Current consumption +24 V external | 200 mA |
| Supported wire size | Solid: 0.05-2.5 mm², 30-12 AWG Stranded: 0.05-1.5 mm², 30-12 AWG Recommended torque: 0.5-0.6 Nm Stripping length 6-7.5mm, 0.24-0.30 inch |
Environment and certification
| CE mark | Yes |
| Electrical safety | IEC 61131-2, UL 61010-1, UL 61010-2-201 |
| Hazardous Location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
| Marine certification | ABS, BV, DNV-GL, LR |
| Protection rating | IP20 according to IEC 60529 |
| Corrosive atmosphere ISA-S71.04 | G3 |
| Climatic operating conditions | 0 to +55 °C (Storage -40 to +70 °C), RH=5 to 95 % no condensation, IEC/EN 61131-2 |
| Pollution degree | Degree 2, IEC 60664-1 |
| Mechanical operating conditions | IEC/EN 61131-2 |
| EMC | EN 61000-6-4 and EN 61000-6-2 |
| Overvoltage categories | IEC/EN 60664-1, EN 50178 |
| Equipment class | Class I according to IEC 61140; (earth protected) |
| Max ambient temperature | 55 °C (131 °F), for vertical mounting 40 °C (104 °F) |
| RoHS compliance | DIRECTIVE/2011/65/EU (EN 50581:2012) |
| WEEE compliance | DIRECTIVE/2012/19/EU |