Contactor ABB AX115-30-11
Khởi động từ A145-30-11 220-230V 50Hz / 230-240V 60Hz
General Information
-
- Extended Product Type: A145-30-11 220-230V 50Hz / 230-240V 60Hz
-
- Product ID: 1SFL471001R8011
-
- EAN: 7320500203286
-
- Catalog Description: A145-30-11 220-230V 50Hz / 230-240V 60Hz Contactor
-
- Long Description: A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V.Operated with control voltage, versions from 24….690 AC, 50 and 60 Hz
Categories
- Products » Low Voltage Products and Systems » Control Products » Contactors » Block Contactors
Ordering
-
- Customs Tariff Number: 85364900
-
- Replacement Product ID (NEW): 1SFL447002R1311
Popular Downloads
-
- Data Sheet, Technical Information: 1SBC100122C0202
-
- Instructions and Manuals: 1SFC380003-89
-
- Dimension Diagram: 53540923-7
Dimensions
-
- Product Net Width: 111.5 mm
-
- Product Net Depth: 160.0 mm
-
- Product Net Height: 196.0 mm
-
- Product Net Weight: 3.500 kg
Technical
-
- Number of Main Contacts NO: 3
-
- Number of Main Contacts NC: 0
-
- Number of Auxiliary Contacts NO: 1
-
- Number of Auxiliary Contacts NC: 1
-
- Rated Operational Voltage: Main Circuit 690 V
-
- Rated Frequency (f): Main Circuit 50/60 Hz
-
- Conventional Free-air Thermal Current (Ith): acc. to IEC 60947-4-1, Open Contactors q = 40 °C 250 A
-
- Rated Operational Current AC-1 (Ie):
- (690 V) 55 °C 230 A
(690 V) 40 °C 250 A
(1000 V) 40 °C 180 A
(1000 V) 55 °C 180 A
(690 V) 70 °C 180 A
(1000 V) 70 °C 180 A
-
- Rated Operational Current AC-3 (Ie):
- (1000 V) 55 °C 80 A
(415 V) 55 °C 145 A
(690 V) 55 °C 120 A
(220 / 230 / 240 V) 55 °C 145 A
(440 V) 55 °C 145 A
(380 / 400 V) 55 °C 145 A
(500 V) 55 °C 145 A
-
- Rated Operational Power AC-3 (Pe):
- (500 V) 90 kW
(220 / 230 / 240 V) 45 kW
(690 V) 110 kW
(380 / 400 V) 75 kW
(440 V) 75 kW
(415 V) 75 kW
-
- Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1: 8 x Ie AC-3
-
- Rated Making Capacity AC-3 acc. to IEC 60947-4-1: 10 x Ie AC-3
-
- Short-Circuit Protective Devices: gG Type Fuses 315 A
-
- Rated Short-time Withstand Current (Icw):
- at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 280 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 800 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1800 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 600 A
-
- Maximum Breaking Capacity:
- cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1500 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1200 A
-
- Maximum Electrical Switching Frequency:
- AC-3 300 cycles per hour
AC-1 300 cycles per hour
AC-2 / AC-4 150 cycles per hour
-
- Rated Operational Current DC-1 (Ie):
- (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
-
- Rated Operational Current DC-3 (Ie):
- (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
-
- Rated Operational Current DC-5 (Ie):
- (110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
-
- Rated Insulation Voltage (Ui):
- acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
-
- Rated Impulse Withstand Voltage (Uimp):
- Main Circuit 8 kV
-
- Mechanical Durability:
- 5 million
-
- Maximum Mechanical Switching Frequency:
- 3600 cycles per hour
-
- Coil Operating Limits:
- (acc. to IEC 60947-4-1) 0.85 x Uc Min. … 1.1 x Uc Max. (at θ ≤ 70 °C) °C
-
- Rated Control Circuit Voltage (Uc):
- 60 Hz 230 … 240 V
50 Hz 220 … 230 V
-
- Coil Consumption:
- Pull-in at Max. Rated Control Circuit Voltage 60 Hz 600 V·A
Holding at Max. Rated Control Circuit Voltage 50 Hz 35 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 550 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 40 V·A